07G.06.DN32

Regulating group with mixing valve fitted to be actuated - reversible - DN 32 - actuator with constant temperature regulator - t

Preassembled pump group for fixed-point regulation and circulation of mixed fluid. Allows the circulation of the thermal fluid, coming from the primary circuit, by keeping the temperature at a pre-set value (fixed-point) through the help of a mixing valve and a fixed-point actuator with integrated controller and probe. It is used in heating systems in general and radiant panel systems. The group is composed of a pump, flow/return shut-off valves, motorizable mixing valve, fixed-point actuator, flow/return temperature gauges, anti-thermosiphon check valve, thermal insulation. In this group the differential by-pass valve can be installed only externally. The group is reversible (the flow line can be exchanged with the return line).

Working temperature range: 5–90 °C

Max working pressure: 10 bar

Connections: female EN 10226-1/male ISO 228-1

Connection centre distance: 125 mm

Pump:  Grundfos UPM3 AUTO L 32-70 180  

            Grundfos UPML AUTO 32-105 180

            Grundfos UPSO 32-65 180 (Extra EU)

Suitable fluids: water, glycol solutions (max 30%)

Temperature gauge scale: 0–120 °C

CODICE_ARTICOLOsizeKv pumpNPC
x----
07G03206YG 2 M - G 1 1/4 F18UPM3 AUTO 32-70 1801
07G03206FG 2 M - G 1 1/4 F18UPML AUTO 32-105 1801
07G03206TG 2 M - G 1 1/4 F18(Extra EU) UPSO 32-65 1801
07G03206XG 2 M - G 1 1/4 F18SENZA POMPA1